03/2/2024 08:20 GMT: Network come back in the rack
All the machines regained their network access. The datacenter replied that they had a power failure on their B feed due to power supplier. The A feed constantly had power. Unfortunately our switch in Hydro66 datacenter is powered only on B feed due to OCP rack constraints so the switch only went down and was powered up again at 08:20 when power came back on B feed.
03/2/2024 05:23 GMT: All machines in Hydro66 lost their network access
Our monitoring system detected all the machines in Hydro66 lost their network access. We asked the datacenter what was the issue.